Product Details:
Payment & Shipping Terms:
|
Voltage Rating (Uo/U): | 500V | Temperature Rating: | -10°C To 250°C |
---|---|---|---|
Conductor: | Solid Plain Copper Conductor | Insulation: | Magnesium Oxide |
Sheath: | Copper Tube | Jacket: | Non Jacketed |
Multi Core MICC Mineral Insulated Cable , 500V Non Jacketed Fire Survival Cable
APPLICATION
Mineral Insulated Cables offer a lifetime, ageless and fireproof electric cable solution that are used to protect essential ‘lifecritical’ circuits in:
• High Rise Buildings
• Tunnels
• Airports
• Towers
• Mass Rapid Transit Systems
MICC Mineral Insulated Cable – Material Construction
• An outer sheath consisting of a continuous seamless copper tube with a melting point of 1083 deg C
• A magnesium oxide insulant with a melting point of 2800 deg C
• 99.9% electrolytic copper conductors with a melting point of 1083 deg C
ADVANTAGE
• Pliable
• Mechanically superior
• Fireproof
• Waterproof
• Explosion Proof
• Radiation Resistant
• Lighter in weight
• Can operate in low temperatures
We supply the full range of LSF (Low Smoke & Fume) outer coverings.
Used for identification purposes where cables are run on the surface of walls or cable trayplates. They are usually Red in colour for fire protection, or the standard Orange. We can also supply a range of other colours on request.
Construction | Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath. |
Operating Temperature | -10degC to +250degC |
Core Identification | Coloured sleeving available |
Lengths | 100/500m. Special lengths available on request. |
Sheath Colour | N/A |
Manufacturing Standard | BS EN 60702-1 |
Code of Practice/ Guide to Use |
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 & power applications see special notes) |
Fire Tests | BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z BS 8491 |
Emissions and Flame Propagation |
In its bare form there are no emissions |
DIMENSIONS
Number and Conductor Size | Cable Diameter | Current Ratings | Nominal Lenght |
Weight | |||
Bare Cable | LSF Served Cable |
Bare Cable | LSF Served Cable |
Bare Cable | LSF Served Cable |
||
mm² | mm | mm | A | A | m | Kg/Km | Kg/Km |
2x1.0 | 5.1 | 6.4 | 17.5 | 19.5 | 800 | 104 | 125 |
2x1.5 | 5.7 | 7 | 22.5 | 25 | 800 | 130 | 153 |
2x2.5 | 6.6 | 7.9 | 30 | 33 | 600 | 179 | 205 |
2x4.0 | 7.7 | 9.2 | 40 | 44 | 450 | 248 | 287 |
3x1.0 | 5.8 | 7.1 | 15 | 16.5 | 800 | 135 | 159 |
3x1.5 | 6.4 | 7.7 | 19 | 21 | 650 | 168 | 193 |
3x2.5 | 7.3 | 8.8 | 25 | 28 | 500 | 224 | 261 |
4x1.0 | 6.3 | 7.6 | 14.5 | 16 | 700 | 161 | 187 |
4x1.5 | 7 | 8.3 | 19 | 21 | 550 | 202 | 230 |
4x2.5 | 8.1 | 9.6 | 25 | 28 | 400 | 278 | 319 |
7x1.0 | 7.6 | 9.1 | 10 | 11 | 650 | 233 | 271 |
7x1.5 | 8.4 | 9.9 | 12.5 | 14 | 530 | 291 | 333 |
7x2.5 | 9.7 | 11.2 | 17 | 19 | 400 | 407 | 455 |
Contact Person: achi