Product Details:
Payment & Shipping Terms:
|
Voltage Rating: | 300/500V | Operating Temperature: | Fixed: -15ºC To +70°C |
---|---|---|---|
Minimum Bending Radius: | Flexed: 10 X Overall Diameter | Sheath Colour: | Black |
Conductor: | Class 5 Flexible Copper Conductor | Insulation: | LSZH (Low Smoke Zero Halogen) |
Bedding: | LSZH (Low Smoke Zero Halogen) | Braiding: | GSWB (Galvanized Steel Wire Braid) |
Sheath: | LSZH (Low Smoke Zero Halogen) |
BS EN/IEC 60332-3 Standard Flexible Control Cable SY LSZH GSWB Cable
APPLICATION
Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines, conveyors and for computer units. Suitable for flexible use in conditions of light mechanical stress. Can be used outdoors when protected against direct sunlight, and in dry or moist conditions indoors. The braided screen offers mechanical protection and a level of electro-magnetic shielding. The galvanized coating helps protect against corrosion. For installations where fire, smoke emissions and toxic fumes create a potential risk to life and equipment.
SY control cables are not suitable for fixed wiring applications requiring compliance with the regulations set out in BS7671.
CABLE STANDARDS
VDE0250, BS EN/IEC 60332-3, BS EN/IEC 60754-1 and 2,
BS EN 60754-1 and 2, BS EN/IEC 61034-1, BS EN 60228,
BS EN 50363
Note
SY Cables are not suitable for direct connection into the main service fuse.
DIMENSIONS
UNI-Cables PART NO. |
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA |
NOMINAL THICKNESS OF INSULATION |
NOMINAL THICKNESS OF BEDDING |
NOMINAL DIAMETER OF GSWB |
NOMINAL THICKNESS OF SHEATH |
NOMINAL OVERALL DIAMETER |
NOMINAL WEIGHT |
mm² | mm | mm | mm | mm | mm | kg/km | ||
UNISYLSZH2015 | 2 | 1.5 | 0.5 | 0.5 | 0.24 | 0.8 | 8 | 109 |
UNISYLSZH3010 | 3 | 1 | 0.5 | 0.5 | 0.24 | 1 | 8 | 114 |
UNISYLSZH3015 | 3 | 1.5 | 0.5 | 0.5 | 0.24 | 1 | 9 | 138 |
UNISYLSZH3025 | 3 | 2.5 | 0.6 | 0.5 | 0.24 | 1 | 10 | 188 |
UNISYLSZH3040 | 3 | 4 | 0.6 | 0.6 | 0.24 | 1 | 12 | 256 |
UNISYLSZH3060 | 3 | 6 | 0.7 | 0.6 | 0.24 | 1.1 | 14 | 352 |
UNISYLSZH4015 | 4 | 1.5 | 0.5 | 0.5 | 0.24 | 1 | 10 | 161 |
UNISYLSZH4025 | 4 | 2.5 | 0.6 | 0.5 | 0.24 | 1 | 11 | 223 |
UNISYLSZH4040 | 4 | 4 | 0.6 | 0.6 | 0.24 | 1 | 13 | 310 |
UNISYLSZH4060 | 4 | 6 | 0.7 | 0.6 | 0.24 | 1.1 | 15 | 430 |
UNISYLSZH5015 | 5 | 1.5 | 0.5 | 0.5 | 0.24 | 1 | 10 | 189 |
UNISYLSZH5025 | 5 | 2.5 | 0.6 | 0.6 | 0.24 | 1 | 12 | 264 |
UNISYLSZH5060 | 5 | 6 | 0.7 | 0.6 | 0.24 | 1.2 | 16 | 523 |
UNISYLSZH510 | 5 | 10 | 0.8 | 0.8 | 0.3 | 1.2 | 20 | 822 |
UNISYLSZH516 | 5 | 16 | 0.9 | 0.8 | 0.3 | 1.4 | 24 | 1217 |
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA | MAXIMUM DIAMETER OF WIRES IN CONDUCTOR |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
mm² | mm | Plain Wires ohms/km |
1 | 0.21 | 19.5 |
1.5 | 0.26 | 13.3 |
2.5 | 0.26 | 7.98 |
4 | 0.31 | 4.95 |
6 | 0.31 | 3.3 |
10 | 0.41 | 1.91 |
16 | 0.41 | 1.21 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity at 30oC
NOMINAL CROSS SECTIONAL AREA mm² |
CURRENT CARRYING CAPACITY | |
In Conduit | In Air | |
Amps | Amps | |
1 | 12 | 20 |
1.5 | 15 | 24 |
2.5 | 20 | 32 |
4 | 25 | 42 |
6 | 33 | 54 |
10 | 45 | 73 |
16 | 61 | 98 |
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm2 |
TWO CORE CABLE DC mV/A/m |
SINGLE-PHASE TWO CORE CABLE AC mV/A/m |
THREE-PHASE THREE OR FOUR CORE CABLE AC mV/A/m |
1 | 44 | 44 | 38 |
1.5 | 29 | 29 | 25 |
2.5 | 18 | 18 | 15 |
4 | 11 | 11 | 9.5 |
6 | 7.3 | 7.3 | 6.4 |
10 | 4.4 | 4.4 | 3.8 |
16 | 2.8 | 2.8 | 2.4 |
DE-RATING FACTORS
NO. OF CORES | 5 | 7 | 10 | 14 | 19 | 24 | 44 | 48 |
DE-RATING FACTOR | 0.72 | 0.63 | 0.56 | 0.51 | 0.45 | 0.42 | 0.34 | 0.33 |
Contact Person: achi